ZHT-FRVV防火系统电缆

所在地: 安徽省 滁州市
发布时间: 2018-11-28
详细信息
产地anhjiehao

防火系统电缆
Special Cable For Fire Resistant System
本产品适用于0.6/1kv及以下的高层建筑物、地铁、隧道、剧场、人防工程、石化系统等所作输配电线路或火灾报警设备、通信设备等应急设施的供电线路及信号控制线路。电缆除低烟无卤高阻燃特性外,还应能处在火焰燃烧中正常运行180min,当火灾发生时,不发生短路和断路故障,一直保障电力供给,维持系统运行。并且燃烧时烟雾透光率高、毒性低,从而显示其防火和消防救生的功能。
    It can be used not only to transmit and distribute power on the power line of 0.6/1kv voltage or below for high-rise building, subway, tunnel, theater, civil air defense engineering, petrochemical system, but also as power supply wire and signal control circuit of emergency facilities such as power transmission and distribution systems, fire alarm equipment and communications equipment and so on. Besides of features of LSZH and high flame resistance, it can also normally operate within 180min under the condition of flame burning. When the fire occurs, short-circuit and open circuit faults would not happen. It could endure continually supplying power and maintain the normal operation of system. During the process of burning, high light transmittance and low toxicity of cable can be considered as an evidence of functions of fireproofing safety and fire rescue.
一、产品执行标准 Q/ZH09.06-2010
    Executive standard: enterprise standard
二、型号
    Type
    ZHT-FRVV—防火电缆
    ZHT-FRVV— type special cable for fire resistance
使用特性
Characteristics
1、交流额定电压:U0/U  0.6/1kv
A.C. rated voltage: U0/U  0.6/1kv
2、工作温度:电缆导体长期工作温度为70℃。
Long-term working temperature of cable conductor shall be 70℃.
3、敷设温度:电缆敷设温度不低于0℃。
Environment temperature for installation shall be no less than 0℃.
4、弯曲半径:电缆弯曲半径不低于电缆外径的15倍。
Bending radium of cable shall be no less than 15 times that of cable outer diameter.
5、阻燃、耐火特性:符合GB19666-2005。
Flame resistance and fire resistance characteristics shall meet the requirements speculated in GB19666-2005 standard.
性能参数表
    Performance parameter

单位
Unit20℃时导体直流电阻≤
Conductor DC Resistance at 20℃截面
Cross section1.54.0电阻
Resistance12.14.61试验电压
Test voltage3.5KV,5min不击穿。
Finished cable shall endure 3.5kv voltage test for 5 min without puncture.MΩ耐火特性
Fire-resistant propertiesA类(火焰温度750试验90min,2A 熔丝不断)
Type A (flame temperature of 750 test 180min, 2A fuse continued)


电缆示意图

     The figure of cable structure

注意事项

     Notes:
施工时严格防止电缆损伤,降低产品性能。
Cable damage and performance reduction are strictly prevented during installation.

交货要求

     Delivery requirement
允许根据双方协议长度交货;长度误差不超过±5%。
Delivery length of cable depends on both agreements with length error allowance of ±5%